Key points for designing the minimum continuous flow (MCF) bypass line when multiple centrifugal pumps are operated in parallel

May 07, 2025 Leave a message

In centrifugal pump systems, to prevent the pumps from running at low or even zero flow for a long time, a minimum continuous flow (MCF) protection is usually set. Especially when multiple pumps are running in parallel, the MCF protection strategy requires a more rigorous design to ensure that all pumps can operate in a safe area to avoid problems such as overheating, vibration, or seal damage.

 

Parallel pump system

 

When two or more centrifugal pumps are running in parallel:
The inlet pressure of all pumps is the same (shared suction port)
The outlet pressure of all pumps is the same (shared water outlet main)
Total system flow = the sum of the output flow of each pump
As shown in the figure below, when two pumps are connected in parallel, the total system flow is the sum of the flow of each pump, but the head is the same:

Typical Pumping System -Two Pumps Connected in Parallel

 

Typical Head-Flow curve for Centrifugal Pump A or Pump B

 

Why is MCF protection important?

Centrifugal pumps must not operate at a flow rate less than MCF for a long time, otherwise, it will cause:

Abnormal motor load

01

Local overheating of the pump body

02

Failure of mechanical seals

03

Water hammer or vibration problems

04

To this end, we usually achieve minimum flow protection through bypass return design, the main methods include:

 
 

Continuous return (orifice plate installed)

 
 
 

Automatic return valve (ARV)

 
 
 

Control valve + flow monitoring

 

Key points in designing multi-pump shared bypass

 

When multiple pumps share one MCF bypass line, the most important design points are:

1. Correctly calculate the return flow
If the minimum flow of each pump is q m³/h, and the number of pumps in parallel operation is n,
the bypass pipe and orifice plate should be designed and selected according to the total minimum flow:
MCF total flow = n × q m³/h

to design and select.

 

IF Number of Pumps Operating in Parallel = n
IF Total flow from "n" pumps operating in Parallel = Q[m³/h]
RULE Flow contributed by each Pump = Q/ n [ m³/h ]..... theoretically

Pump Performance blocked discharge when Orifice and bypass line is Sized for 2x MCF

 

2. Do not design the total bypass according to the MCF of a single pump
If the bypass system is mistakenly designed to allow only the minimum flow rate (q m³/h) of one pump to pass, then when all pumps are running, the reflux capacity is insufficient and each pump can only reflux q/2, which is in a dangerous working area.

Pump Performance blocked discharge when Orifice and MCF bypass is Sized for 1 x MCF

 

Alternative: Use a flow control system

 

If a control valve + flow meter is used instead of a continuous return flow, the controller setting should be set to:
Controller setting = n × q m³/h
To ensure that the system does not fall below the total MCF in any regulation state.

Common MCF Bypass with Flow Control System

 

Summary and suggestions

 

* It is feasible to share the MCF bypass line when multiple pumps are connected in parallel, but it must be designed according to the total minimum flow.
* Unreasonable design may cause the pump to operate in a dangerous area, reduce its life, or even damage the equipment.
* Whether it is an orifice plate reflux, ARV, or control valve system, "total flow protection" must be considered during design.
* It is particularly important to conduct dynamic simulation evaluation in the early stage of system design.

 

If you need to obtain design optimization suggestions or customized solutions for this type of pump group, please contact us.
We have been focusing on centrifugal pump manufacturing for more than 30 years, providing you with more professional, reliable, and cost-effective solutions.